Fire Alarm Wire Size Chart

Maximum one-way run length for a 24 V notification circuit by wire gauge and alarm load, before the end-of-line voltage falls below the 16 V appliance minimum. Lengths are the conservative case with the full load at the far end. This is the voltage-drop physics read as "how far can I go" instead of "how much voltage is left."

Maximum run length by gauge & load

Computed · 24 VDC
Maximum one-way run length (ft) before the end-of-line voltage reaches the 16 V floor, by wire gauge and total alarm load, from a 24 V source using NEC Chapter 9 Table 8 copper resistance. Rounded down to the nearest 10 ft.
Alarm load18 AWG16 AWG14 AWG12 AWG
0.5 A1020 ft1630 ft2600 ft4140 ft
1.0 A510 ft810 ft1300 ft2070 ft
1.5 A340 ft540 ft860 ft1380 ft
2.0 A250 ft400 ft650 ft1030 ft
Lengths assume the full load concentrated at the end of the run (conservative). Use the panel's minimum regulated output as the source voltage and the device's own minimum for a final design; a heavier gauge or a split circuit extends the reach.

How to use it

Total up the alarm current on the circuit, pick the row at or above it, and read across to the gauge you plan to pull — the number is the farthest the last appliance can sit from the panel. If your run is longer, move down a gauge (18 → 16 → 14 → 12 AWG), split the appliances onto another circuit to cut the per-circuit load, or add a NAC booster power supply closer to the load. The underlying formula and the voltage-remaining view are on the NAC voltage drop chart, and typical appliance currents by candela are on the NAC current draw chart.

Common questions

What wire gauge for a fire alarm NAC circuit?

It depends on the alarm load and how far the circuit runs. Heavier wire carries lower resistance, so it reaches farther before the end-of-line voltage drops below the 16 V appliance minimum on a 24 V system. At a 1.0 A load, 18 AWG reaches about 510 ft while 12 AWG reaches about 2070 ft. Contractors commonly run 18, 16, 14, or 12 AWG fire alarm cable.

How far can a fire alarm circuit run?

As far as the voltage budget allows: the run length where the end-of-line voltage would fall to the appliance minimum. That distance shrinks as the load rises and grows as the wire gets heavier. The chart gives the maximum one-way length for each gauge and load combination; beyond it, you drop to a heavier gauge, split the load across more circuits, or add a booster power supply.

Does this chart assume the whole load is at the end?

These lengths use the total circuit load as if concentrated at the far end, the standard conservative simplification. When appliances are spread along the run, the true drop is smaller, so the real reach is a bit farther — but designing to the concentrated-load figure keeps a safety margin. The exact answer comes from a point-by-point voltage-drop calculation.

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice. Our team sets it up for your shop and walks you through your next real job.

Request access →