Grounding Electrode Conductor (GEC) Size Chart
The grounding electrode conductor is sized from the service — not the breaker. Find the largest ungrounded service-entrance conductor below (or the equivalent area when service conductors are paralleled) and read off the minimum copper or aluminum GEC. Values per NEC Table 250.66, identical across the 2014 through 2023 editions.
Minimum GEC by service-entrance conductor size
| Service — copper | Service — aluminum/CCA | GEC — copper | GEC — aluminum/CCA |
|---|---|---|---|
| ≤ 2 | ≤ 1/0 | 8 AWG | 6 AWG |
| 1 to 1/0 | 2/0 to 3/0 | 6 AWG | 4 AWG |
| 2/0 to 3/0 | 4/0 to 250 | 4 AWG | 2 AWG |
| 4/0 to 350 | 300 to 500 | 2 AWG | 1/0 AWG |
| 400 to 600 | 600 to 900 | 1/0 AWG | 3/0 AWG |
| 700 to 1100 | 1000 to 1750 | 2/0 AWG | 4/0 AWG |
| over 1100 | over 1750 | 3/0 AWG | 250 kcmil |
How to read this chart
Start from the largest ungrounded service-entrance conductor — the phase conductor, not the neutral — and pick the row it falls in, using the copper or aluminum column to match your service conductor material. Where the service is paralleled, add the circular mils of the parallel set first: two 350 kcmil copper conductors per phase read as 700 kcmil, which lands in the 700 to 1100 row. The GEC itself may be copper or aluminum regardless of what the service conductors are — but per NEC 250.64(A), aluminum grounding electrode conductors can't be used in direct contact with masonry or earth, or within 18 inches of the earth outdoors, which in practice keeps most electrode runs copper.
By electrode type
| Electrode | Minimum GEC | NEC cite |
|---|---|---|
| Metal underground water pipe | Full Table 250.66 value | 250.66 |
| Building steel (in-ground support structure) | Full Table 250.66 value | 250.66 |
| Ground rod, pipe, or plate | 6 AWG Cu / 4 AWG Al max | 250.66(A) |
| Concrete-encased electrode (Ufer) | 4 AWG Cu max | 250.66(B) |
| Ground ring | Size of the ring (ring ≥ 2 AWG Cu) | 250.66(C) |
| Bonding jumper between electrodes | Same rule as the electrode served | 250.53(C) |
GEC vs. EGC — don't mix the tables
This chart sizes the conductor to the earth electrodes. The ground wire run with a circuit is the equipment grounding conductor, sized from the breaker rating under NEC 250.122 — see the ground wire (EGC) size chart. Using 250.122 for an electrode run typically oversizes small services and undersizes large ones, so it fails inspection in both directions. There is also a near-twin of this table for the main, system, and supply-side bonding jumpers and the grounded conductor — identical rows until the largest services, where it keeps growing instead of capping at 3/0: see the bonding jumper size chart. As always, verify against the code edition your jurisdiction enforces.
Common questions
What size grounding electrode conductor do I need for a 200 amp service?
A typical 200 A dwelling service is wired with 2/0 copper or 4/0 aluminum service-entrance conductors. Either lands on the same row of Table 250.66: a 4 AWG copper (or 2 AWG aluminum) grounding electrode conductor. And if that GEC runs solely to a ground rod, 250.66(A) caps it at 6 AWG copper regardless — the water-pipe or building-steel connection is what needs the full 4 AWG.
What is the difference between the GEC and the EGC?
The grounding electrode conductor (GEC) connects the electrical system to the earth electrodes — rod, water pipe, footing steel — and is sized from the SERVICE-ENTRANCE CONDUCTOR size per Table 250.66. The equipment grounding conductor (EGC) is the ground wire run with each circuit back to the panel and is sized from the BREAKER rating per Table 250.122. Different job, different table, different size.
Do I ever need a GEC larger than 6 AWG to a ground rod?
No. When the grounding electrode conductor is the sole connection to a rod, pipe, or plate electrode, NEC 250.66(A) says it is not required to be larger than 6 AWG copper (or 4 AWG aluminum) — a rod cannot dissipate more current than a 6 AWG can deliver. The same logic caps a sole connection to a concrete-encased electrode at 4 AWG copper (250.66(B)) and to a ground ring at the size of the ring conductor (250.66(C)).
RUN THE NUMBERS
Run your whole job on the same numbers
These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.
See what NORDIX does →