NEMA L6-20 — 250 V, 20 A Twist-Lock Plug & Receptacle
NEMA L6-20 is a twist-locking configuration per NEMA WD-6: 250 V, 20 A, 2-pole 3-wire grounding. Server-rack PDUs, machine tools. The receptacle is L6-20R, the matching plug L6-20P.
No free-licensed face diagram exists for this configuration yet — locking faces are not on Wikimedia Commons. The specs below still identify it unambiguously.
Specifications
- Configuration
- L6-20
- Series
- Locking (L / twist-lock)
- Voltage rating
- 250 V
- Amp rating
- 20 A
- Poles / wires
- 2P–3W
- Neutral
- No
- Equipment ground
- Yes
- Max load (at rating)
- 250 V × 20 A = 5,000 VA
- Continuous (80%)
- 4,000 VA
Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.
Where you meet it
Server-rack PDUs, machine tools. Family L6 overall: hvac, machine tools, server pdus (l6-30). The locking blades twist in and cannot vibrate or pull loose — the reason generators, stage rigs, and equipment connections spec the L series over its straight-blade cousins.
RELATED CONFIGURATIONS
See every configuration on the full NEMA plug & receptacle chart →
Common questions
What is the difference between L6-20R and L6-20P?
The letter is the device: L6-20R is the receptacle (outlet), L6-20P is the plug on the cord. Both share the same configuration — 250 V, 20 A, 2-pole 3-wire grounding, twist-locking blades.
Does NEMA L6-20 have a neutral and a ground?
No neutral — the 250 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).