NEMA L9-20600 V, 20 A Twist-Lock Plug & Receptacle

NEMA L9-20 is a twist-locking configuration per NEMA WD-6: 600 V, 20 A, 2-pole 3-wire grounding. 600 V single-phase, hot–hot–ground. The receptacle is L9-20R, the matching plug L9-20P.

No free-licensed face diagram exists for this configuration yet — locking faces are not on Wikimedia Commons. The specs below still identify it unambiguously.

Specifications

Configuration
L9-20
Series
Locking (L / twist-lock)
Voltage rating
600 V
Amp rating
20 A
Poles / wires
2P–3W
Neutral
No
Equipment ground
Yes
Max load (at rating)
600 V × 20 A = 12,000 VA
Continuous (80%)
9,600 VA

Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.

Where you meet it

600 V single-phase, hot–hot–ground. The locking blades twist in and cannot vibrate or pull loose — the reason generators, stage rigs, and equipment connections spec the L series over its straight-blade cousins.

RELATED CONFIGURATIONS

See every configuration on the full NEMA plug & receptacle chart →

Common questions

What is the difference between L9-20R and L9-20P?

The letter is the device: L9-20R is the receptacle (outlet), L9-20P is the plug on the cord. Both share the same configuration — 600 V, 20 A, 2-pole 3-wire grounding, twist-locking blades.

Does NEMA L9-20 have a neutral and a ground?

No neutral — the 600 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.

See what NORDIX does →