SLA Battery Size Chart

The standard sealed lead-acid (SLA / VRLA) battery capacities stocked for fire alarm control panels. Each battery is 12 V; two in series make the 24 V the panel runs on. Size the battery by calculating the required amp-hours and rounding up to the next capacity here. These capacities come from manufacturer catalogs — NFPA 72 sets the required Ah, not the battery size.

Standard 12 V SLA capacities

VRLA / manufacturer
Nominal amp-hour capacities of 12 V SLA batteries used in fire alarm panels, wired in pairs for 24 V. The middle column flags the sizes battery calculators commonly round up to.
CapacityCommon round-up sizeTypical use
4 AhSmall single-panel systems
7 AhYesThe most common panel battery
12 AhYesCommon mid-size panels
18 AhYesLarger panels and short NAC loads
26 AhYesMulti-NAC and addressable systems
33 AhYesLarge systems (35 Ah is a common variant)
40 AhYesLarge systems / extended standby
55 AhVoice systems and long standby periods
100 AhLargest common single battery
Terminal type varies by capacity and manufacturer — small batteries use F1/F2 faston tabs, larger ones use nut-and-bolt (insert) terminals. 35 Ah is a common variant of the 33 Ah size. Physical dimensions vary by maker and are not shown.

Sizing and replacing

You never pick a battery size directly — you calculate it. The standby battery calculation gives a required amp-hour figure; you round it up to the next capacity on this list. Rounding down would leave the system short of its required standby-plus-alarm runtime once the battery ages.

Both batteries in a panel must be the same capacity and are replaced as a matched pair — mixing an old battery with a new one drags the pair down to the weaker cell. Batteries are typically replaced on a schedule (commonly every 3–5 years) regardless of apparent condition, because SLA capacity fades well before the battery fails outright.

Common questions

What size battery does a fire alarm panel use?

Fire alarm panels use 12 V sealed lead-acid (SLA/VRLA) batteries wired in pairs to make 24 V. The standard capacities are 4, 7, 12, 18, 26, 33, 40, 55, and 100 Ah; 7 Ah is the most common. You calculate the required amp-hours and install the next standard size at or above it.

Why are there two batteries in a fire alarm panel?

Each SLA battery is 12 V nominal, and a fire alarm system runs on 24 V, so two identical batteries are wired in series (12 V + 12 V = 24 V). Both must be the same capacity and replaced as a matched pair.

How do I know which capacity to buy?

Run the standby battery calculation for your system, then round the result up to the next capacity on this list — never down. The calculation adds 24 hours of standby current to 5 minutes (or 15 for voice) of alarm current and multiplies by the aging factor.

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice. Our team sets it up for your shop and walks you through your next real job.

Request access →