Transformer Overcurrent Protection (1000 V or Less)
The maximum overcurrent device for a transformer is a percentage of its rated current, set by NEC Table 450.3(B): protect from the primary side alone, or protect both windings and buy a bigger primary device. Compute the winding's full-load amps, apply the percentage below, and pick the device from the standard 240.6(A) ratings — rounding up only where Note 1 says you may.
Maximum OCPD as % of rated current
| Protection scheme | Winding | Rated current | Max OCPD | Next size up? |
|---|---|---|---|---|
| Primary OCPD only | Primary | 9 A or more | 125% | Yes — Note 1 |
| Primary OCPD only | Primary | Less than 9 A | 167% | No |
| Primary OCPD only | Primary | Less than 2 A | 300% | No |
| Primary + secondary OCPDs | Primary | Any | 250% | No |
| Primary + secondary OCPDs | Secondary | 9 A or more | 125% | Yes — Note 1 |
| Primary + secondary OCPDs | Secondary | Less than 9 A | 167% | No |
Worked maximum sizes — three-phase, 480 V Δ to 208Y/120 V
| kVA | Primary FLA (A) | Max primary — no secondary OCPD | Max primary — with secondary OCPD | Secondary FLA (A) | Max secondary OCPD |
|---|---|---|---|---|---|
| 15 | 18.0 | 25 A | 45 A | 41.6 | 60 A |
| 30 | 36.1 | 50 A | 90 A | 83.3 | 110 A |
| 45 | 54.1 | 70 A | 125 A | 124.9 | 175 A |
| 75 | 90.2 | 125 A | 225 A | 208.2 | 300 A |
| 112.5 | 135.3 | 175 A | 300 A | 312.3 | 400 A |
| 150 | 180.4 | 250 A | 450 A | 416.4 | 600 A |
| 225 | 270.6 | 350 A | 600 A | 624.5 | 800 A |
| 300 | 360.8 | 500 A | 800 A | 832.7 | 1200 A |
| 500 | 601.4 | 800 A | 1200 A | 1387.9 | 2000 A |
| 750 | 902.1 | 1200 A | 2000 A | 2081.8 | 3000 A |
| 1,000 | 1202.8 | 1600 A | 3000 A | 2775.7 | 4000 A |
Worked maximum sizes — single-phase, 480 V to 120/240 V
| kVA | Primary FLA (A) | Max primary — no secondary OCPD | Max primary — with secondary OCPD | Secondary FLA (A) | Max secondary OCPD |
|---|---|---|---|---|---|
| 15 | 31.3 | 40 A | 70 A | 62.5 | 80 A |
| 25 | 52.1 | 70 A | 125 A | 104.2 | 150 A |
| 37.5 | 78.1 | 100 A | 175 A | 156.3 | 200 A |
| 50 | 104.2 | 150 A | 250 A | 208.3 | 300 A |
| 75 | 156.3 | 200 A | 350 A | 312.5 | 400 A |
| 100 | 208.3 | 300 A | 500 A | 416.7 | 600 A |
One OCPD or two — what the schemes mean
Every transformer has a secondary winding; the scheme names describe how many overcurrent devices you install. Primary OCPD only means the breaker or fuses ahead of the transformer are the sole protection — so they're held to a tight 125%, because they must catch secondary-side overloads reflected through the windings. Primary + secondary OCPDs adds a device on the secondary (typically the panelboard main); that device handles overload at 125% of secondary FLA, which frees the primary device to run as large as 250% — enough to ride through magnetizing inrush without nuisance tripping. That's the scheme nearly every delta-wye install uses in practice, since the secondary equipment needs a main anyway.
450.3 protects the transformer — not everything behind it
This table answers one question: how big may the device be so the transformer survives. It deliberately says nothing about the secondary conductors — those follow the tap rules of 240.21(C) — or a panelboard on the secondary, which needs its own protection per 408.36. On a common delta-wye transformer the primary device cannot protect either one, which is why real installs almost always end up in the primary-and-secondary row even though the primary-only column exists. Size the windings first with the transformer sizing calculator, then apply this table to each side.
Over 1000 volts — a different table
Medium-voltage transformers take NEC Table 450.3(A), whose limits swing on three extra variables — whether the location is supervised, the transformer's impedance band, and whether the device is a fuse or a breaker — with separate columns again for secondaries over and under 1000 V. See the MV transformer protection chart for the full 450.3(A) grid.
Common questions
What size breaker for a 75 kVA, 480 V to 208Y/120 V transformer?
Primary full-load current is 75,000 ÷ (480 × 1.732) ≈ 90 A; with primary-and-secondary protection the primary breaker may be up to 250% ≈ 225 A, or with primary-only protection 125% ≈ 113 A → a 125 A breaker via Note 1. Secondary FLA is 75,000 ÷ (208 × 1.732) ≈ 208 A; 125% ≈ 260 A → a 300 A device via Note 1. Remember 450.3 protects the transformer — the secondary conductors and panelboard have their own rules (240.21(C), 408.36).
When can I skip the secondary overcurrent device?
Table 450.3(B) allows primary-only protection at 125% (167% / 300% for small primaries). In practice you rarely get to use it on three-phase installs: the secondary conductors still need protection per 240.21(C), and a panelboard on the secondary requires protection per 408.36 — a delta-wye transformer primary OCPD cannot protect those. The primary-only column mostly earns its keep on single-phase 2-wire and control transformers.
Why do small transformers get 167% and 300%?
Magnetizing inrush. A transformer with a primary current under 9 A would need a tiny OCPD at 125%, and a tiny OCPD trips on the inrush every time the transformer energizes. The code trades protection margin for startability: up to 167% below 9 A and 300% below 2 A — and those cells are hard ceilings, with no Note 1 round-up.
RUN THE NUMBERS
Run your whole job on the same numbers
These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.
See what NORDIX does →