Transformer Overcurrent Protection (1000 V or Less)

The maximum overcurrent device for a transformer is a percentage of its rated current, set by NEC Table 450.3(B): protect from the primary side alone, or protect both windings and buy a bigger primary device. Compute the winding's full-load amps, apply the percentage below, and pick the device from the standard 240.6(A) ratings — rounding up only where Note 1 says you may.

Maximum OCPD as % of rated current

NEC 450.3(B)
Maximum overcurrent-device rating or setting as a percentage of the winding's rated current, for transformers 1000 V and less (values per NEC Table 450.3(B)). The scheme describes which OCPDs are installed — every transformer has a secondary; 'primary OCPD only' means the primary device is the sole overcurrent protection. Round up = Note 1: where 125% doesn't land on a standard 240.6(A) rating, the next higher standard rating is permitted; all other cells are hard ceilings.
Protection schemeWindingRated currentMax OCPDNext size up?
Primary OCPD onlyPrimary9 A or more125%Yes — Note 1
Primary OCPD onlyPrimaryLess than 9 A167%No
Primary OCPD onlyPrimaryLess than 2 A300%No
Primary + secondary OCPDsPrimaryAny250%No
Primary + secondary OCPDsSecondary9 A or more125%Yes — Note 1
Primary + secondary OCPDsSecondaryLess than 9 A167%No
The 250% primary cell also carries Note 3: a transformer with coordinated thermal overload protection by the manufacturer can exceed it under conditions spelled out in the note. Check the nameplate before leaning on that.

Worked maximum sizes — three-phase, 480 V Δ to 208Y/120 V

450.3(B) × 240.6(A)
Maximum permitted OCPD per NEC 450.3(B) for the standard dry-type kVA ladder, computed from exact full-load currents and the standard 240.6(A) ratings. Primary-only column at 125% with Note 1 round-up; primary-with-secondary at the 250% ceiling rounded down; secondary at 125% with Note 1 round-up.
kVAPrimary
FLA (A)
Max primary —
no secondary OCPD
Max primary —
with secondary OCPD
Secondary
FLA (A)
Max secondary
OCPD
1518.025 A45 A41.660 A
3036.150 A90 A83.3110 A
4554.170 A125 A124.9175 A
7590.2125 A225 A208.2300 A
112.5135.3175 A300 A312.3400 A
150180.4250 A450 A416.4600 A
225270.6350 A600 A624.5800 A
300360.8500 A800 A832.71200 A
500601.4800 A1200 A1387.92000 A
750902.11200 A2000 A2081.83000 A
1,0001202.81600 A3000 A2775.74000 A
Maximums, not recommendations — smaller devices are always compliant and often chosen for coordination. Every row's currents are 9 A or more, so the 125% / 250% / 125% cells govern throughout.

Worked maximum sizes — single-phase, 480 V to 120/240 V

450.3(B) × 240.6(A)
Maximum permitted OCPD per NEC 450.3(B) for common single-phase kVA ratings, computed from exact full-load currents and the standard 240.6(A) ratings, same rules as above.
kVAPrimary
FLA (A)
Max primary —
no secondary OCPD
Max primary —
with secondary OCPD
Secondary
FLA (A)
Max secondary
OCPD
1531.340 A70 A62.580 A
2552.170 A125 A104.2150 A
37.578.1100 A175 A156.3200 A
50104.2150 A250 A208.3300 A
75156.3200 A350 A312.5400 A
100208.3300 A500 A416.7600 A
Maximums, not recommendations — smaller devices are always compliant and often chosen for coordination. Every row's currents are 9 A or more, so the 125% / 250% / 125% cells govern throughout.

One OCPD or two — what the schemes mean

Every transformer has a secondary winding; the scheme names describe how many overcurrent devices you install. Primary OCPD only means the breaker or fuses ahead of the transformer are the sole protection — so they're held to a tight 125%, because they must catch secondary-side overloads reflected through the windings. Primary + secondary OCPDs adds a device on the secondary (typically the panelboard main); that device handles overload at 125% of secondary FLA, which frees the primary device to run as large as 250% — enough to ride through magnetizing inrush without nuisance tripping. That's the scheme nearly every delta-wye install uses in practice, since the secondary equipment needs a main anyway.

450.3 protects the transformer — not everything behind it

This table answers one question: how big may the device be so the transformer survives. It deliberately says nothing about the secondary conductors — those follow the tap rules of 240.21(C) — or a panelboard on the secondary, which needs its own protection per 408.36. On a common delta-wye transformer the primary device cannot protect either one, which is why real installs almost always end up in the primary-and-secondary row even though the primary-only column exists. Size the windings first with the transformer sizing calculator, then apply this table to each side.

Over 1000 volts — a different table

Medium-voltage transformers take NEC Table 450.3(A), whose limits swing on three extra variables — whether the location is supervised, the transformer's impedance band, and whether the device is a fuse or a breaker — with separate columns again for secondaries over and under 1000 V. See the MV transformer protection chart for the full 450.3(A) grid.

Common questions

What size breaker for a 75 kVA, 480 V to 208Y/120 V transformer?

Primary full-load current is 75,000 ÷ (480 × 1.732) ≈ 90 A; with primary-and-secondary protection the primary breaker may be up to 250% ≈ 225 A, or with primary-only protection 125% ≈ 113 A → a 125 A breaker via Note 1. Secondary FLA is 75,000 ÷ (208 × 1.732) ≈ 208 A; 125% ≈ 260 A → a 300 A device via Note 1. Remember 450.3 protects the transformer — the secondary conductors and panelboard have their own rules (240.21(C), 408.36).

When can I skip the secondary overcurrent device?

Table 450.3(B) allows primary-only protection at 125% (167% / 300% for small primaries). In practice you rarely get to use it on three-phase installs: the secondary conductors still need protection per 240.21(C), and a panelboard on the secondary requires protection per 408.36 — a delta-wye transformer primary OCPD cannot protect those. The primary-only column mostly earns its keep on single-phase 2-wire and control transformers.

Why do small transformers get 167% and 300%?

Magnetizing inrush. A transformer with a primary current under 9 A would need a tiny OCPD at 125%, and a tiny OCPD trips on the inrush every time the transformer energizes. The code trades protection margin for startability: up to 167% below 9 A and 300% below 2 A — and those cells are hard ceilings, with no Note 1 round-up.

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.

See what NORDIX does →