Wire Dimensions Chart — Diameter & Area by Insulation

The physical size of an insulated conductor — its approximate diameter and the cross-sectional area it occupies — for the four insulation groups you actually pull: THHN/THWN, XHHW, TW/THW/THHW, and RHH/RHW. These are the areas every conduit fill calculation is built on. Values per NEC Chapter 9, Table 5, 14 AWG through 1000 kcmil.

Insulated conductor dimensions

NEC CH.9 T5
Approximate diameter (inches) and cross-sectional area (square inches) by conductor size and insulation group (values per NEC Chapter 9, Table 5; conventional Class B stranding). THHN column covers THHN/THWN/THWN-2; XHHW covers XHHW/XHHW-2; THW covers TW/THW/THHW/THW-2; RHW covers RHH/RHW/RHW-2 with outer covering.
SizeTHHN
dia (in)
THHN
area (in²)
XHHW
dia (in)
XHHW
area (in²)
THW
dia (in)
THW
area (in²)
RHW
dia (in)
RHW
area (in²)
14 AWG0.1110.00970.1330.01390.1330.01390.1930.0293
12 AWG0.1300.01330.1520.01810.1520.01810.2120.0353
10 AWG0.1640.02110.1760.02430.1760.02430.2360.0437
8 AWG0.2160.03660.2360.04370.2360.04370.3260.0835
6 AWG0.2540.05070.2740.05900.3040.07260.3640.1041
4 AWG0.3240.08240.3220.08140.3520.09730.4120.1333
3 AWG0.3520.09730.3500.09620.3800.11340.4400.1521
2 AWG0.3840.11580.3820.11460.4120.13330.4720.1750
1 AWG0.4460.15620.4420.15340.4920.19010.5820.2660
1/0 AWG0.4860.18550.4820.18250.5320.22230.6220.3039
2/0 AWG0.5320.22230.5280.21900.5780.26240.6680.3505
3/0 AWG0.5840.26790.5800.26420.6300.31170.7200.4072
4/0 AWG0.6420.32370.6380.31970.6880.37180.7780.4754
250 kcmil0.7110.39700.7050.39040.7650.45960.8950.6291
300 kcmil0.7660.46080.7600.45360.8200.52810.9500.7088
350 kcmil0.8170.52420.8110.51660.8710.59581.0010.7870
400 kcmil0.8640.58630.8580.57820.9180.66191.0480.8626
500 kcmil0.9490.70730.9430.69841.0030.79011.1331.0082
600 kcmil1.0510.86761.0530.87091.1130.97291.2431.2135
700 kcmil1.1220.98871.1240.99231.1841.10101.3141.3561
750 kcmil1.1561.04961.1581.05321.2181.16521.3481.4272
800 kcmil1.1881.10851.1901.11221.2501.22721.3801.4957
900 kcmil1.2521.23111.2541.23511.3141.35611.4441.6377
1000 kcmil1.3101.34781.3121.35191.3721.47841.5021.7719
Compact-stranded conductors are smaller — they take NEC Chapter 9, Table 5A, not this chart. The RHH/RHW variants without outer covering (asterisked in the code book) also differ. Bare conductors are dimensioned under Chapter 9, Table 8 — see the wire resistance chart.

What these numbers are for

Conduit fill is an area problem: sum the square-inch areas of every conductor in the raceway — the highlighted THHN columns are the everyday case — and compare the total against the usable fill area of your conduit on the conduit fill chart. The conduit fill calculator runs the same Table 5 data, mixed sizes and insulations included, and recommends a minimum trade size. The diameter column earns its keep on jam checks — three same-size conductors whose combined diameters sit near the conduit's inner diameter can wedge during the pull — and anywhere physical fit matters: gutters, KOs, and lug throats.

Reading it right

Diameters are the code's approximate values at conventional Class B stranding — a given manufacturer's THHN may run a few mils tighter or looser, so check the spec sheet when the fit is critical. Watch the insulation crossover: THHN is the slim choice through 6 AWG, but from 4 AWG up XHHW is slightly smaller, which can save a trade size on a crowded feeder. And don't borrow rows across variants — the RHW column here is the with-covering construction; the asterisked no-covering variants and all compact-stranded conductors (Table 5A) have their own, smaller numbers.

Common questions

What is the diameter and area of 12 AWG THHN?

A 12 AWG THHN/THWN conductor is approximately 0.130 inches in diameter with a cross-sectional area of 0.0133 square inches (NEC Chapter 9, Table 5). That area number is what conduit fill math runs on — sixteen of them fit the 40% fill of 3/4-inch EMT.

Is THHN or XHHW physically smaller?

It flips at 4 AWG. In branch-circuit sizes THHN is the slimmer wire — 12 AWG THHN is 0.0133 in² against XHHW’s 0.0181 in². From 4 AWG up, XHHW’s single XLPE wall edges out THHN’s nylon-jacketed PVC: a 500 kcmil XHHW is 0.6984 in² versus 0.7073 in² for THHN. On a tight feeder pull through existing conduit, that few-percent difference sometimes decides the wire type.

Do these dimensions apply to compact-stranded conductors?

No. Table 5 assumes conventional (Class B) stranding. Compact-stranded aluminum and copper conductors are drawn to smaller overall diameters and take their dimensions from NEC Chapter 9, Table 5A — always noticeably smaller. Likewise, an individual manufacturer’s actual OD can differ slightly from these approximate values; for a critical fit, use the manufacturer’s spec sheet.

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.

See what NORDIX does →