Ampacity Correction & Adjustment Factors
The ampacity tables assume 30°C air and no more than three current-carrying conductors together. Real installations get hot attics and packed raceways, and these two multipliers are how the code accounts for both: the ambient temperature correction of Table 310.15(B)(1) and the conductor-bundling adjustment of Table 310.15(C)(1). Multiply them against the base ampacity — starting from the column matching the conductor's insulation rating.
Ambient temperature correction
| Ambient (°C) | Ambient (°F) | 60°C rated | 75°C rated | 90°C rated |
|---|---|---|---|---|
| 10 or less | 50 or less | 1.29 | 1.20 | 1.15 |
| 11–15 | 51–59 | 1.22 | 1.15 | 1.12 |
| 16–20 | 60–68 | 1.15 | 1.11 | 1.08 |
| 21–25 | 69–77 | 1.08 | 1.05 | 1.04 |
| 26–30 | 78–86 | 1.00 | 1.00 | 1.00 |
| 31–35 | 87–95 | 0.91 | 0.94 | 0.96 |
| 36–40 | 96–104 | 0.82 | 0.88 | 0.91 |
| 41–45 | 105–113 | 0.71 | 0.82 | 0.87 |
| 46–50 | 114–122 | 0.58 | 0.75 | 0.82 |
| 51–55 | 123–131 | 0.41 | 0.67 | 0.76 |
| 56–60 | 132–140 | — | 0.58 | 0.71 |
| 61–65 | 141–149 | — | 0.47 | 0.65 |
| 66–70 | 150–158 | — | 0.33 | 0.58 |
| 71–75 | 159–167 | — | — | 0.50 |
| 76–80 | 168–176 | — | — | 0.41 |
| 81–85 | 177–185 | — | — | 0.29 |
More than three current-carrying conductors
| Current-carrying conductors | Multiplier | % of base ampacity |
|---|---|---|
| 1–3 | 1.00 | 100% |
| 4–6 | 0.80 | 80% |
| 7–9 | 0.70 | 70% |
| 10–20 | 0.50 | 50% |
| 21–30 | 0.45 | 45% |
| 31–40 | 0.40 | 40% |
| 41 and above | 0.35 | 35% |
Running a derate, start to finish
Take the base ampacity from the wire ampacity chart in the column matching the insulation — 90°C for THHN — then multiply by both factors: ambient first, bundling second (order doesn't matter; they multiply). The result must clear the load, must not exceed the termination-rated ampacity (usually the 75°C column), and small conductors keep their 240.4(D) breaker caps. The ampacity & derating calculator runs this exact chain — same factors, same tables — and shows its work.
One non-obvious consequence: derating is why the 90°C column exists for building wire at all. You can rarely terminate at 90°C, but starting the multiplication from the higher number often saves a wire size — 30 A × 0.91 × 0.70 from the 90°C column survives where the same math from the 60°C column fails.
Where the numbers come from
The correction factors aren't arbitrary: each one is the code's own equation — the square root of (conductor rating minus ambient) over (rating minus 30°C) — evaluated at the top of each band, which is why the columns fall off a cliff as the ambient approaches the insulation rating and why a 60°C conductor simply exits the table above 55°C. The bundling factors account for conductors heating each other when they can't shed heat independently; they kick in hard at ten conductors (50%), which is the point where stuffing one more circuit into an existing raceway usually stops being worth it.
Common questions
How do I apply both factors together?
Multiply, starting from the ampacity column matching the conductor insulation — for THHN that is the 90°C column. Example: 12 AWG THHN (30 A at 90°C) with eight current-carrying conductors in a conduit through a 38°C space is 30 × 0.91 × 0.70 = 19.1 A. The final answer must also not exceed what the terminations allow (usually the 75°C ampacity), and the small-conductor breaker caps of 240.4(D) still apply.
Does the neutral count as a current-carrying conductor?
Usually not, sometimes yes. A neutral that carries only the unbalanced current of a multiwire circuit is not counted (NEC 310.15(E)) — but it IS counted when it serves two of the three phases of a wye system, or when the load is mostly nonlinear (drives, electronic ballasts, IT equipment) and harmonic current keeps it loaded. Equipment grounding conductors never count.
What ambient do I use for conduit in the sun on a rooftop?
In the 2020 and later editions, NEC 310.15(B)(2) requires adding 33°C (60°F) to the outdoor ambient for raceways or cables in direct sunlight less than 7/8 inch above the roof — which routinely pushes the corrected ambient into the bands at the bottom of this table. Raise the raceway above 7/8 inch and the adder disappears. Earlier editions used a graduated height table; check the edition your jurisdiction enforces.
RUN THE NUMBERS
Run your whole job on the same numbers
These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.
See what NORDIX does →