Motor Full-Load Current Chart
The code's own motor currents: full-load amperes by horsepower and rated voltage for three-phase induction motors (NEC Table 430.250, 1/2 through 500 HP) and single-phase motors (Table 430.248, 1/6 through 10 HP). Per 430.6(A)(1) these table values — not the nameplate — size the conductors, the short-circuit protection, and the disconnect. Values assume normal-torque motors at usual belted speeds.
Three-phase induction motors (squirrel cage & wound rotor)
| HP | 115 V | 200 V | 208 V | 230 V | 460 V | 575 V | 2300 V |
|---|---|---|---|---|---|---|---|
| 1/2 | 4.4 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 | — |
| 3/4 | 6.4 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 | — |
| 1 | 8.4 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 | — |
| 1½ | 12 | 6.9 | 6.6 | 6 | 3 | 2.4 | — |
| 2 | 13.6 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 | — |
| 3 | — | 11 | 10.6 | 9.6 | 4.8 | 3.9 | — |
| 5 | — | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 | — |
| 7½ | — | 25.3 | 24.2 | 22 | 11 | 9 | — |
| 10 | — | 32.2 | 30.8 | 28 | 14 | 11 | — |
| 15 | — | 48.3 | 46.2 | 42 | 21 | 17 | — |
| 20 | — | 62.1 | 59.4 | 54 | 27 | 22 | — |
| 25 | — | 78.2 | 74.8 | 68 | 34 | 27 | — |
| 30 | — | 92 | 88 | 80 | 40 | 32 | — |
| 40 | — | 120 | 114 | 104 | 52 | 41 | — |
| 50 | — | 150 | 143 | 130 | 65 | 52 | — |
| 60 | — | 177 | 169 | 154 | 77 | 62 | 16 |
| 75 | — | 221 | 211 | 192 | 96 | 77 | 20 |
| 100 | — | 285 | 273 | 248 | 124 | 99 | 26 |
| 125 | — | 359 | 343 | 312 | 156 | 125 | 31 |
| 150 | — | 414 | 396 | 360 | 180 | 144 | 37 |
| 200 | — | 552 | 528 | 480 | 240 | 192 | 49 |
| 250 | — | — | — | — | 302 | 242 | 60 |
| 300 | — | — | — | — | 361 | 289 | 72 |
| 350 | — | — | — | — | 414 | 336 | 83 |
| 400 | — | — | — | — | 477 | 382 | 95 |
| 450 | — | — | — | — | 515 | 412 | 103 |
| 500 | — | — | — | — | 590 | 472 | 118 |
Single-phase motors
| HP | 115 V | 200 V | 208 V | 230 V |
|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 | 7.2 | 4.1 | 4 | 3.6 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8 |
| 1½ | 20 | 11.5 | 11 | 10 |
| 2 | 24 | 13.8 | 13.2 | 12 |
| 3 | 34 | 19.6 | 18.7 | 17 |
| 5 | 56 | 32.2 | 30.8 | 28 |
| 7½ | 80 | 46 | 44 | 40 |
| 10 | 100 | 57.5 | 55 | 50 |
Table value vs. nameplate — the rule that trips people up
NEC 430.6(A)(1) splits motor sizing down the middle: the table values here determine the branch-circuit conductors (125% of FLC per 430.22), the short-circuit and ground-fault protection (430.52), the feeder calculations (430.24), and the disconnect — while the nameplate current sets only the overload protection (430.32). The logic: wiring sized from the standard table doesn't need to change when a motor is replaced with another of the same rating, but the overload device protects the actual winding installed. The motor FLA calculator runs the same table values with the 430.22 conductor minimum computed for you.
Reading the columns
Column voltages are rated motor voltages — read 460 V for a 480 V system, 230 V for 240, 115 V for 120 — and the highlighted 460 V column is where most industrial three-phase work lives. The values assume normal-torque motors at usual belted speeds; high-torque, multispeed, or inverter-duty machines can draw differently, which is one more reason overloads come from the nameplate. Once you have the FLC, the 125% conductor minimum lands on the wire ampacity chart — and remember motor circuits are the classic case where the breaker can legally be far larger than the conductor ampacity, because the overload relay is doing the protecting.
Common questions
What is the full-load current of a 10 HP, 460 V three-phase motor?
14 amperes per Table 430.250 — and that table value, not the nameplate, is what NEC 430.6(A)(1) requires for sizing the branch-circuit conductors (125% of 14 A = 17.5 A minimum ampacity per 430.22) and the short-circuit device. The nameplate current is used for one thing: setting the overload protection.
Why does the chart say 460 V when my system is 480 V?
The columns are rated MOTOR voltages — motors are wound for 460 V on a 480 V system, 230 V on 240, 115 V on 120. The table says its currents are permitted for the matching system-voltage ranges (440–480, 220–240, 110–120, 550–600), so a 480 V system reads the 460 V column. There is no separate 480 V column to look for.
My motor nameplate says a different FLA than the table — which one wins?
Both, for different jobs. Conductors, short-circuit/ground-fault protection, and disconnect sizing use the TABLE value (430.6(A)(1)) precisely so the wiring doesn’t change every time a motor is swapped for one with a slightly different nameplate. Overload protection (430.32) is sized from the NAMEPLATE, because it protects that specific winding. Using the nameplate for conductors is the classic plan-review red flag.
RUN THE NUMBERS
Run your whole job on the same numbers
These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.
See what NORDIX does →