NEMA 15-303Ø 250 V, 30 A Plug & Receptacle

NEMA 15-30 is a straight-blade configuration per NEMA WD-6: 3Ø 250 V, 30 A, 3-pole 4-wire grounding. Three-phase with ground. The receptacle is 15-30R, the matching plug 15-30P.

NEMA 15-30R face diagram
15-30Rreceptacle (outlet face)
NEMA 15-30P face diagram
15-30Pplug (blade face)

Face diagrams by Comrade Mmirg via Wikimedia Commons, CC BY-SA 4.0 / CC0, unmodified.

Specifications

Configuration
15-30
Series
Straight blade
Voltage rating
3Ø 250 V
Amp rating
30 A
Poles / wires
3P–4W
Neutral
No
Equipment ground
Yes
Max load (at rating)
√3 × 250 V × 30 A = 12,990 VA
Continuous (80%)
10,392 VA

Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.

Where you meet it

Three-phase with ground. Blade geometry keys the voltage family physically: a plug from a different voltage class will not enter this receptacle.

RELATED CONFIGURATIONS

15-2015-5015-60Locking twin: L15-30

See every configuration on the full NEMA plug & receptacle chart →

Common questions

What is the difference between 15-30R and 15-30P?

The letter is the device: 15-30R is the receptacle (outlet), 15-30P is the plug on the cord. Both share the same configuration — 3Ø 250 V, 30 A, 3-pole 4-wire grounding.

Does NEMA 15-30 have a neutral and a ground?

No neutral — the 3Ø 250 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).