NEMA 15-303Ø 250 V, 30 A Plug & Receptacle

NEMA 15-30 is a straight-blade configuration per NEMA WD-6: 3Ø 250 V, 30 A, 3-pole 4-wire grounding. Three-phase with ground. The receptacle is 15-30R, the matching plug 15-30P.

NEMA 15-30R face diagram
15-30Rreceptacle (outlet face)
NEMA 15-30P face diagram
15-30Pplug (blade face)

Face diagrams by Comrade Mmirg via Wikimedia Commons, CC BY-SA 4.0 / CC0, unmodified.

Specifications

Configuration
15-30
Series
Straight blade
Voltage rating
3Ø 250 V
Amp rating
30 A
Poles / wires
3P–4W
Neutral
No
Equipment ground
Yes
Max load (at rating)
√3 × 250 V × 30 A = 12,990 VA
Continuous (80%)
10,392 VA

Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.

Where you meet it

Three-phase with ground. Blade geometry keys the voltage family physically: a plug from a different voltage class will not enter this receptacle.

RELATED CONFIGURATIONS

15-2015-5015-60Locking twin: L15-30

See every configuration on the full NEMA plug & receptacle chart →

Common questions

What is the difference between 15-30R and 15-30P?

The letter is the device: 15-30R is the receptacle (outlet), 15-30P is the plug on the cord. Both share the same configuration — 3Ø 250 V, 30 A, 3-pole 4-wire grounding.

Does NEMA 15-30 have a neutral and a ground?

No neutral — the 3Ø 250 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.