NEMA L15-303Ø 250 V, 30 A Twist-Lock Plug & Receptacle

NEMA L15-30 is a twist-locking configuration per NEMA WD-6: 3Ø 250 V, 30 A, 3-pole 4-wire grounding. Three-phase 250 V with ground. The receptacle is L15-30R, the matching plug L15-30P.

No free-licensed face diagram exists for this configuration yet — locking faces are not on Wikimedia Commons. The specs below still identify it unambiguously.

Specifications

Configuration
L15-30
Series
Locking (L / twist-lock)
Voltage rating
3Ø 250 V
Amp rating
30 A
Poles / wires
3P–4W
Neutral
No
Equipment ground
Yes
Max load (at rating)
√3 × 250 V × 30 A = 12,990 VA
Continuous (80%)
10,392 VA

Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.

Where you meet it

Three-phase 250 V with ground. The locking blades twist in and cannot vibrate or pull loose — the reason generators, stage rigs, and equipment connections spec the L series over its straight-blade cousins.

RELATED CONFIGURATIONS

L15-20Straight-blade twin: 15-30

See every configuration on the full NEMA plug & receptacle chart →

Common questions

What is the difference between L15-30R and L15-30P?

The letter is the device: L15-30R is the receptacle (outlet), L15-30P is the plug on the cord. Both share the same configuration — 3Ø 250 V, 30 A, 3-pole 4-wire grounding, twist-locking blades.

Does NEMA L15-30 have a neutral and a ground?

No neutral — the 3Ø 250 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).