NEMA L15-30 — 3Ø 250 V, 30 A Twist-Lock Plug & Receptacle
NEMA L15-30 is a twist-locking configuration per NEMA WD-6: 3Ø 250 V, 30 A, 3-pole 4-wire grounding. Three-phase 250 V with ground. The receptacle is L15-30R, the matching plug L15-30P.
No free-licensed face diagram exists for this configuration yet — locking faces are not on Wikimedia Commons. The specs below still identify it unambiguously.
Specifications
- Configuration
- L15-30
- Series
- Locking (L / twist-lock)
- Voltage rating
- 3Ø 250 V
- Amp rating
- 30 A
- Poles / wires
- 3P–4W
- Neutral
- No
- Equipment ground
- Yes
- Max load (at rating)
- √3 × 250 V × 30 A = 12,990 VA
- Continuous (80%)
- 10,392 VA
Load figures are the arithmetic of the device rating at unity power factor. Continuous loads (3 hours or more) are limited to 80% of the circuit rating per NEC 210.19/210.20 — and the branch circuit behind the receptacle comes from the load calculation and conductor sizing, not from the plug face.
Where you meet it
Three-phase 250 V with ground. The locking blades twist in and cannot vibrate or pull loose — the reason generators, stage rigs, and equipment connections spec the L series over its straight-blade cousins.
RELATED CONFIGURATIONS
See every configuration on the full NEMA plug & receptacle chart →
Common questions
What is the difference between L15-30R and L15-30P?
The letter is the device: L15-30R is the receptacle (outlet), L15-30P is the plug on the cord. Both share the same configuration — 3Ø 250 V, 30 A, 3-pole 4-wire grounding, twist-locking blades.
Does NEMA L15-30 have a neutral and a ground?
No neutral — the 3Ø 250 V rating means the circuit runs line-to-line with no neutral. It carries an equipment grounding conductor (the extra wire beyond the poles).