Safety Switch Ratings Chart

Disconnect safety switch sizes from 30 to 1200 amperes with their horsepower ratings — heavy-duty fusible with the standard and time-delay-fuse maximums at 240, 480, and 600 V, the non-fusible ratings, the general-duty 240 V table, and the general-duty vs heavy-duty decision chart. Values are the UL 98 listing ratings that Eaton, Square D, and Siemens publish in common; every cell here is confirmed across at least two of those catalogs, and the handful of cells where catalogs disagree are footnoted. The switch nameplate governs the install.

Heavy-duty fusible — HP ratings (std / max with time-delay fuses)

UL 98
Three-pole heavy-duty (600 V class) fusible switch horsepower ratings by ampere size. Each cell is standard HP / maximum HP — the maximum applies only with dual-element time-delay fuses installed. Single-phase 240 V column included through 200 A (not published above).
Switch1φ 240 V
std / max
3φ 240 V
std / max
3φ 480 V
std / max
3φ 600 V
std / max
30 A1.5 / 33 / 7.55 / 157.5 / 20
60 A3 / 107.5 / 1515 / 3015 / 50
100 A7.5 / 1515 / 3025 / 6030 / 75
200 A15 / 1525 / 6050 / 12560 / 150
400 A50 / 125100 / 250125 / 350
600 A75 / 200150 / 400200 / 500
800 A100 / 250200 / 500250 / 500
1200 A100 / 250200 / 500250 / 500
Catalog disagreements, printed as the two-manufacturer value: at 100 A / 600 V the max is 75 HP per Eaton and Siemens (Square D's current Digest prints 100); at 800/1200 A / 240 V the 250 HP max is Square D + Siemens (Eaton publishes no time-delay max there). Above 1200 A you're into bolted-pressure switch territory.

Heavy-duty non-fusible — HP ratings

UL 98
Non-fusible switches carry a single three-phase HP rating per voltage — no fuse, no std/max split; overcurrent protection lives upstream. Dashes: not double-witnessed across catalogs.
Switch240 V480 V600 V
30 A102030
60 A205060
100 A4075100
200 A60125150
400 A125250350
600 A200400500
800 A500500
1200 A500500
Note the small sizes out-rate their fusible twins: 60 A at 480 V is 50 HP here vs 30 HP fusible-max — the fusible rating is capped by what a fuse in that switch can start, not by the blades.

General-duty (240 V) fusible — HP ratings

UL 98
General-duty switches are a 240 V class and stop at 600 A. Cells are standard HP / maximum HP with time-delay fuses.
Switch1φ 240 V
std / max
3φ 240 V
std / max
30 A1.5 / 33 / 7.5
60 A3 / 107.5 / 15
100 A7.5 / 1515 / 30
200 A15 / 1525 / 60
400 A50 / 125
600 A75 / 200
Identical to the heavy-duty 240 V column through 400 A; at 600 A the 200 HP max is Eaton + Siemens (Square D prints 150).

General duty vs heavy duty

UL 98 / KS 1
What actually separates the two switch families. Both are quick-make/quick-break, horsepower-rated, load-break devices under UL 98.
AttributeGeneral dutyHeavy duty
Voltage class240 Vac (some 250 Vdc)Up to 600 Vac; 250/600 Vdc
Ampere range30–600 A30–1200 A (bolted-pressure switches beyond)
Short-circuit rating (with fuses)10 kA with Class H/K; 100 kA with Class R, J, or T current-limiting fuses10 kA with Class H/K; 200 kA with Class R, J, T, or L
EnclosuresNEMA 1 and 3R onlyNEMA 1, 3R, 12, 4/4X (painted, stainless, non-metallic), plus 7/9 hazardous-location variants
Fuse provisionsClass H/K standard; Class R with rejection kitClass H/K/R standard with Class J provisions; 800–1200 A take Class L bolt-in
ConstructionQuick-make/quick-break, HP ratedAdds visible double-break blades, arc chutes, defeatable dual cover interlocks, hookstick handles, auxiliary contacts
Where it belongsResidential and light commercial — A/C units, appliances, lighting loadsIndustrial and commercial motor loads, hostile environments, service continuity

How to size a disconnect

Two checks, both mandatory. The ampere check: 115% of the motor's table full-load current (from the motor FLA chart), rounded up to the switch ladder — the rule and its exceptions live on the motor disconnect rules chart. The horsepower check: the switch's HP rating at your voltage must cover the motor, on the column matching your fuse type. The ampere math often lands on a switch whose standard HP rating falls short — that's the time-delay-fuse column's job, and it's why dual-element fuses are the default in motor circuits. The motor circuit data chart runs both checks for every standard motor.

Common questions

What do the two horsepower numbers on a safety switch mean?

Every fusible switch carries a dual HP rating: the standard rating, which applies with ordinary non-time-delay fuses, and a higher maximum rating that applies only when dual-element time-delay fuses are installed. A 30 A heavy-duty switch at 480 V is 5 HP standard but 15 HP with time-delay fuses — the fuse choice, not the switch hardware, is what unlocks the difference, because time-delay fuses ride through motor inrush at a smaller ampere size.

What size disconnect do I need for a 50 HP, 480 V motor?

By the NEC math: 65 A table FLC × 115% = 74.8 A minimum, so a 100 A switch. The HP ratings agree — a 100 A heavy-duty switch at 480 V is rated 25 HP standard and 60 HP with time-delay fuses, so it carries 50 HP only on the time-delay rating; with non-time-delay fuses you would need the 200 A switch. Check both the ampere rule and the HP line.

When is a general-duty switch acceptable instead of heavy-duty?

On 240 V systems in residential and light-commercial service — the A/C disconnect on a house wall is the classic general-duty install. The moment the system is 480 V, general duty is out (it is a 240 V class device). Heavy-duty is the default spec for industrial motor loads, anywhere you need NEMA 12/4X or hazardous-location enclosures, high fault current with Class R/J/T/L fusing, or auxiliary contacts.

Why does a non-fusible switch have a higher HP rating than the same size fusible switch?

At the small sizes it does — a 60 A heavy-duty switch at 480 V is 50 HP non-fusible but only 30 HP even with time-delay fuses. The fusible rating is limited by what fuse can both fit the switch and survive motor inrush; the non-fusible switch is rated purely on its blades' ability to break locked-rotor current, since something upstream provides the overcurrent protection. From 200 A up, the two converge.

Are safety switch HP ratings the same for every manufacturer?

Almost — the ratings are UL 98 listing values and Eaton, Square D, and Siemens publish matching tables nearly cell for cell. A few cells genuinely differ between catalogs (Square D currently lists 100 HP where others list 75 at 100 A/600 V; general-duty 600 A max is 200 HP for Eaton and Siemens but 150 for Square D). This chart prints the value at least two manufacturers agree on — the nameplate on the switch you actually install governs.

RUN THE NUMBERS

Run your whole job on the same numbers

These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.

See what NORDIX does →