Motor Circuit Data Chart
One row per motor: table full-load current, minimum 75°C copper conductor (at 125% of FLC), maximum dual-element fuse and inverse-time breaker (175% and 250%, rounded up per Exception 1), NEMA starter size, and minimum disconnect switch (115% of FLC) — the complete NEC 430 stack for three-phase squirrel-cage motors at 208, 230, 460, and 575 V. Every column derives from the same verified tables behind our FLA, ampacity, and starter charts, so this page and those pages cannot disagree.
460 V three-phase
The workhorse industrial voltage.
| HP | FLC (A) | Min. ampacity (125%) | Copper wire (75°C) | Max TD fuse (A) | Max breaker (A) | NEMA starter | Disconnect (A) |
|---|---|---|---|---|---|---|---|
| 1/2 | 1.1 | 1.38 | 14 AWG | 15 | 15 | 00 | 30 |
| 3/4 | 1.6 | 2 | 14 AWG | 15 | 15 | 00 | 30 |
| 1 | 2.1 | 2.63 | 14 AWG | 15 | 15 | 00 | 30 |
| 1.5 | 3 | 3.75 | 14 AWG | 15 | 15 | 00 | 30 |
| 2 | 3.4 | 4.25 | 14 AWG | 15 | 15 | 00 | 30 |
| 3 | 4.8 | 6 | 14 AWG | 15 | 15 | 0 | 30 |
| 5 | 7.6 | 9.5 | 14 AWG | 15 | 20 | 0 | 30 |
| 7.5 | 11 | 13.75 | 14 AWG | 20 | 30 | 1 | 30 |
| 10 | 14 | 17.5 | 14 AWG | 25 | 35 | 1 | 30 |
| 15 | 21 | 26.25 | 10 AWG | 40 | 60 | 2 | 30 |
| 20 | 27 | 33.75 | 10 AWG | 50 | 70 | 2 | 60 |
| 25 | 34 | 42.5 | 8 AWG | 60 | 90 | 2 | 60 |
| 30 | 40 | 50 | 8 AWG | 70 | 100 | 3 | 60 |
| 40 | 52 | 65 | 6 AWG | 100 | 150 | 3 | 60 |
| 50 | 65 | 81.25 | 4 AWG | 125 | 175 | 3 | 100 |
| 60 | 77 | 96.25 | 3 AWG | 150 | 200 | 4 | 100 |
| 75 | 96 | 120 | 1 AWG | 175 | 250 | 4 | 200 |
| 100 | 124 | 155 | 2/0 AWG | 225 | 350 | 4 | 200 |
| 125 | 156 | 195 | 3/0 AWG | 300 | 400 | 5 | 200 |
| 150 | 180 | 225 | 4/0 AWG | 350 | 450 | 5 | 400 |
| 200 | 240 | 300 | 350 kcmil | 450 | 600 | 5 | 400 |
| 250 | 302 | 377.5 | 500 kcmil | 600 | 800 | 6 | 400 |
| 300 | 361 | 451.25 | 2 × 4/0 AWG | 700 | 1000 | 6 | 600 |
| 350 | 414 | 517.5 | 2 × 300 kcmil | 800 | 1200 | 6 | 600 |
| 400 | 477 | 596.25 | 2 × 350 kcmil | 1000 | 1200 | 6 | 600 |
| 450 | 515 | 643.75 | 2 × 400 kcmil | 1000 | 1600 | 7 | 600 |
| 500 | 590 | 737.5 | 2 × 500 kcmil | 1200 | 1600 | 7 | 800 |
230 V three-phase
Small-shop and legacy 240 V systems.
| HP | FLC (A) | Min. ampacity (125%) | Copper wire (75°C) | Max TD fuse (A) | Max breaker (A) | NEMA starter | Disconnect (A) |
|---|---|---|---|---|---|---|---|
| 1/2 | 2.2 | 2.75 | 14 AWG | 15 | 15 | 00 | 30 |
| 3/4 | 3.2 | 4 | 14 AWG | 15 | 15 | 00 | 30 |
| 1 | 4.2 | 5.25 | 14 AWG | 15 | 15 | 00 | 30 |
| 1.5 | 6 | 7.5 | 14 AWG | 15 | 15 | 00 | 30 |
| 2 | 6.8 | 8.5 | 14 AWG | 15 | 20 | 0 | 30 |
| 3 | 9.6 | 12 | 14 AWG | 20 | 25 | 0 | 30 |
| 5 | 15.2 | 19 | 14 AWG | 30 | 40 | 1 | 30 |
| 7.5 | 22 | 27.5 | 10 AWG | 40 | 60 | 1 | 30 |
| 10 | 28 | 35 | 10 AWG | 50 | 70 | 2 | 60 |
| 15 | 42 | 52.5 | 6 AWG | 80 | 110 | 2 | 60 |
| 20 | 54 | 67.5 | 4 AWG | 100 | 150 | 3 | 100 |
| 25 | 68 | 85 | 4 AWG | 125 | 175 | 3 | 100 |
| 30 | 80 | 100 | 3 AWG | 150 | 200 | 3 | 100 |
| 40 | 104 | 130 | 1 AWG | 200 | 300 | 4 | 200 |
| 50 | 130 | 162.5 | 2/0 AWG | 250 | 350 | 4 | 200 |
| 60 | 154 | 192.5 | 3/0 AWG | 300 | 400 | 5 | 200 |
| 75 | 192 | 240 | 250 kcmil | 350 | 500 | 5 | 400 |
| 100 | 248 | 310 | 350 kcmil | 450 | 700 | 5 | 400 |
| 125 | 312 | 390 | 600 kcmil | 600 | 800 | 6 | 400 |
| 150 | 360 | 450 | 2 × 4/0 AWG | 700 | 1000 | 6 | 600 |
| 200 | 480 | 600 | 2 × 350 kcmil | 1000 | 1200 | 6 | 600 |
208 V three-phase
Wye systems fed from 120/208 V services; starters use the NEMA 200 V column.
| HP | FLC (A) | Min. ampacity (125%) | Copper wire (75°C) | Max TD fuse (A) | Max breaker (A) | NEMA starter | Disconnect (A) |
|---|---|---|---|---|---|---|---|
| 1/2 | 2.4 | 3 | 14 AWG | 15 | 15 | 00 | 30 |
| 3/4 | 3.5 | 4.38 | 14 AWG | 15 | 15 | 00 | 30 |
| 1 | 4.6 | 5.75 | 14 AWG | 15 | 15 | 00 | 30 |
| 1.5 | 6.6 | 8.25 | 14 AWG | 15 | 20 | 00 | 30 |
| 2 | 7.5 | 9.38 | 14 AWG | 15 | 20 | 0 | 30 |
| 3 | 10.6 | 13.25 | 14 AWG | 20 | 30 | 0 | 30 |
| 5 | 16.7 | 20.88 | 12 AWG | 30 | 45 | 1 | 30 |
| 7.5 | 24.2 | 30.25 | 10 AWG | 45 | 70 | 1 | 30 |
| 10 | 30.8 | 38.5 | 8 AWG | 60 | 80 | 2 | 60 |
| 15 | 46.2 | 57.75 | 6 AWG | 90 | 125 | 3 | 60 |
| 20 | 59.4 | 74.25 | 4 AWG | 110 | 150 | 3 | 100 |
| 25 | 74.8 | 93.5 | 3 AWG | 150 | 200 | 3 | 100 |
| 30 | 88 | 110 | 2 AWG | 175 | 225 | 4 | 200 |
| 40 | 114 | 142.5 | 1/0 AWG | 200 | 300 | 4 | 200 |
| 50 | 143 | 178.75 | 3/0 AWG | 300 | 400 | 5 | 200 |
| 60 | 169 | 211.25 | 4/0 AWG | 300 | 450 | 5 | 200 |
| 75 | 211 | 263.75 | 300 kcmil | 400 | 600 | 5 | 400 |
| 100 | 273 | 341.25 | 500 kcmil | 500 | 700 | 6 | 400 |
| 125 | 343 | 428.75 | 2 × 4/0 AWG | 700 | 1000 | 6 | 400 |
| 150 | 396 | 495 | 2 × 250 kcmil | 700 | 1000 | 6 | 600 |
| 200 | 528 | 660 | 2 × 400 kcmil | 1000 | 1600 | — | 800 |
575 V three-phase
Canadian and mining supply; starter sizes match 460 V (ICS 2 rates them together).
| HP | FLC (A) | Min. ampacity (125%) | Copper wire (75°C) | Max TD fuse (A) | Max breaker (A) | NEMA starter | Disconnect (A) |
|---|---|---|---|---|---|---|---|
| 1/2 | 0.9 | 1.13 | 14 AWG | 15 | 15 | 00 | 30 |
| 3/4 | 1.3 | 1.63 | 14 AWG | 15 | 15 | 00 | 30 |
| 1 | 1.7 | 2.13 | 14 AWG | 15 | 15 | 00 | 30 |
| 1.5 | 2.4 | 3 | 14 AWG | 15 | 15 | 00 | 30 |
| 2 | 2.7 | 3.38 | 14 AWG | 15 | 15 | 00 | 30 |
| 3 | 3.9 | 4.88 | 14 AWG | 15 | 15 | 0 | 30 |
| 5 | 6.1 | 7.63 | 14 AWG | 15 | 20 | 0 | 30 |
| 7.5 | 9 | 11.25 | 14 AWG | 20 | 25 | 1 | 30 |
| 10 | 11 | 13.75 | 14 AWG | 20 | 30 | 1 | 30 |
| 15 | 17 | 21.25 | 12 AWG | 30 | 45 | 2 | 30 |
| 20 | 22 | 27.5 | 10 AWG | 40 | 60 | 2 | 30 |
| 25 | 27 | 33.75 | 10 AWG | 50 | 70 | 2 | 60 |
| 30 | 32 | 40 | 8 AWG | 60 | 80 | 3 | 60 |
| 40 | 41 | 51.25 | 6 AWG | 80 | 110 | 3 | 60 |
| 50 | 52 | 65 | 6 AWG | 100 | 150 | 3 | 60 |
| 60 | 62 | 77.5 | 4 AWG | 110 | 175 | 4 | 100 |
| 75 | 77 | 96.25 | 3 AWG | 150 | 200 | 4 | 100 |
| 100 | 99 | 123.75 | 1 AWG | 175 | 250 | 4 | 200 |
| 125 | 125 | 156.25 | 2/0 AWG | 225 | 350 | 5 | 200 |
| 150 | 144 | 180 | 3/0 AWG | 300 | 400 | 5 | 200 |
| 200 | 192 | 240 | 250 kcmil | 350 | 500 | 5 | 400 |
| 250 | 242 | 302.5 | 350 kcmil | 450 | 700 | 6 | 400 |
| 300 | 289 | 361.25 | 500 kcmil | 600 | 800 | 6 | 400 |
| 350 | 336 | 420 | 600 kcmil | 600 | 1000 | 6 | 400 |
| 400 | 382 | 477.5 | 2 × 250 kcmil | 700 | 1000 | 6 | 600 |
| 450 | 412 | 515 | 2 × 300 kcmil | 800 | 1200 | 7 | 600 |
| 500 | 472 | 590 | 2 × 350 kcmil | 1000 | 1200 | 7 | 600 |
How this chart is built
Every column is computed, not transcribed: full-load currents from NEC Table 430.250 (the motor FLA chart), conductor picks from Table 310.16 (the ampacity chart), protection percentages from Table 430.52(C)(1) (the motor circuit protection chart), starter sizes from NEMA ICS 2 (the NEMA starter size chart), and disconnect sizes from the 115% rule against the standard switch ladder (the safety switch ratings chart). Overload protection is deliberately absent — it sizes from the NAMEPLATE current of the specific motor you install, at 115–125% per 430.32, and no table keyed to horsepower can print it honestly.
Common questions
What wire size do I need for a 30 HP, 460 V motor?
The table full-load current is 40 A; conductors size at 125% of that (430.22), so 50 A minimum ampacity — 8 AWG copper at 75°C. Protection: up to a 70 A time-delay fuse or 100 A inverse-time breaker (430.52 with the round-up allowance), a NEMA Size 3 starter, and a 60 A disconnect (115% of FLC). One row of the 460 V table below.
Why is the breaker bigger than the wire ampacity in this chart?
Because motor branch-circuit devices only protect against short circuits and ground faults — they must be large enough to ride the starting inrush. The conductors are protected from overload by the starter’s overload relay at 115–125% of nameplate current, not by the breaker. This split is the whole design of NEC Article 430, and it is why a 10 AWG wire legally lives behind an 80 A breaker in a motor circuit.
Are the fuse and breaker columns requirements or maximums?
Maximums. The chart prints the largest permitted dual-element time-delay fuse (175% of FLC) and inverse-time breaker (250%), each rounded up to the next standard size as Exception 1 allows. Smaller devices are always permitted if they hold the starting current — many engineers spec the fuse at 125–150% for closer protection.
What do the dashes in the starter column mean?
The FLA tables publish motors beyond the NEMA ladder at that voltage — a 200 HP motor at 208 V exceeds Size 6, the largest starter with a 200 V rating. Those motors get engineered starters, solid-state soft starters, or VFDs rather than a catalog NEMA frame.
Can I use this chart for single-phase motors?
No — these tables derive from the three-phase FLC table (430.250). Single-phase full-load currents are far higher per horsepower; get them from the motor FLA chart and run the same percentages: 125% for wire, 175%/250% for protection, 115% for the disconnect.
RUN THE NUMBERS
Run your whole job on the same numbers
These NORDIX tools are a taste of the full platform — bid pipeline, estimating, and job costing that carry your numbers from the first bid to the final invoice.
See what NORDIX does →