Fire alarm design math is code math: NFPA 72 dictates how long the secondary supply must carry the system, what margin sits on top of the calculated amp-hours, and how fast the charger must bring the batteries back. These calculators put that arithmetic in the browser — starting with the standby battery calculation every plan submittal needs, built on per-device standby and alarm currents from a verified manufacturer library, the 24-hour-plus-5-minute durations (15 minutes for voice systems), and the aging correction factor for the code edition your jurisdiction has adopted.

The details these tools sweat are the ones plan reviewers reject packages over: the 2022 edition raised the battery correction factor from ×1.2 to ×1.25, door holders on power that drops on AC loss count toward neither standby nor alarm, and the batteries a panel can legally carry are capped by its listed charger. Results round up to the standard sealed lead-acid sizes panels actually take — two 12 V blocks in series — and print as an AHJ-format submittal sheet with the full math chain shown. Free, browser-based, no account; pair them with the NORDIX fire alarm reference charts when you need the code table rather than a computed answer.